Errors, logging, and debugging

Goal: learn the three ways LXMASTER tells you what is happening — return values, device status reports, and the runtime log — so that when a bring-up fails or a device misbehaves, you can see exactly why.

You met lastError() in your first application. This page turns that into a habit and adds the two other layers of visibility you will lean on constantly.

The three layers of visibility

LayerAnswersHow you get it
Return value + lastError()"Did this call succeed, and if not, why?"Check the bool, print net.lastError().
Device status report"What state did each device end in?"net.reportDeviceStatus(os) after stop().
Runtime log"What happened, step by step, during the run?"Enable cfg.debug.

Start with the first, add the second when a run ends badly, and turn on the third when you need the blow-by-blow.

EtherCAT background: where errors come from

Most failures you will see originate in the EtherCAT bring-up itself, and they carry standard diagnostic codes:

  • AL status codes — when a slave refuses a state transition (say PRE-OP → SAFE-OP), it reports an Application Layer status code explaining why (bad SM config, invalid mailbox, etc.). LXMASTER surfaces these in lastError() and the device status report.
  • CoE abort / error objects — a failed SDO configuration during PRE-OP comes back as a CoE abort code.
  • CiA402 fault code 0x603F — a faulted drive stores a manufacturer fault code here; the device status report prints it.

You do not need to memorize these — the point is that the error strings you print are not generic, they pinpoint the slave and the reason.

Layer 1: return values and lastError()

Every operation that can fail returns a bool. The rule is simple: check it, and print lastError() when it is false.

lxmaster::EcNetwork net(cfg);

if (!net.prepare()) {
std::cerr << "prepare failed: " << net.lastError() << "\n";
return 1;
}
if (!net.start()) {
std::cerr << "start failed: " << net.lastError() << "\n";
return 1;
}

Key properties of lastError():

  • It is thread-safe — safe to read from any thread.
  • It holds the last captured message, so read it immediately after the failing call.
  • During shutdown it also accumulates [shutdown] step failures, so a stop() that could not cleanly walk the bus down still leaves an explanation behind.

Layer 2: the device status report

reportDeviceStatus() prints a per-device end-of-run summary. Because it reports from a snapshot taken while the master was still open, you see what the bus actually looked like at shutdown — not a zeroed-out table:

net.stop();
net.reportDeviceStatus(std::cout);

It surfaces each device's final EtherCAT state and AL status code, a faulted drive's CiA402 fault code (0x603F), and — if the run ended on a bus fault — the break location and the slaves that went silent. This is the first thing to check when a run ends unexpectedly. (Bus faults get their own treatment in Detecting and handling bus faults.)

Layer 3: the runtime log

For a step-by-step trace of bring-up and operation, enable logging on the config. It is off by default to keep the runtime quiet.

lxmaster::NetworkConfig cfg = lxmaster::NetworkConfig::defaults();
cfg.eni.eni_path = "/path/to/bus.eni.xml";

cfg.debug.enabled = true; // master switch
cfg.debug.min_level = ecdev::LogLevel::Info; // Error < Warn < Info < Debug < Trace

With log_file left empty, output goes to the console (Error/Warn to stderr, everything else to stdout). Point it at a path to get a rotating log file instead — ideal for an unattended deployment:

cfg.debug.log_file = "/var/log/myapp/lxmaster.log"; // rotating FileSink

Focusing the log by category

The log is split into subsystems; category_mask selects which ones you want. Narrow it to avoid drowning in output:

// Only bring-up and cyclic/watchdog messages:
cfg.debug.category_mask =
static_cast<std::uint32_t>(ecdev::LogCat::Bringup) |
static_cast<std::uint32_t>(ecdev::LogCat::Cyclic);
Category (ecdev::LogCat)Covers
Bringupprepare()/start() phase walk, INIT/PRE-OP, shutdown milestones
StateESM transitions, AL status
Pdomapping layout, per-cycle PDO dumps
CyclicOP entry, working counter, watchdog, jitter
DcSyncDC phase lock, sync stats
CoeSDO probes, CoE error objects
RtRT scheduling identity

The default (ecdev::kLogCatAll) passes every category.

Level (ecdev::LogLevel)Use when
ErrorSomething failed. Always compiled in.
WarnRecoverable oddity. Always compiled in.
InfoHigh-level progress.
DebugDetailed step tracing.
TraceEverything, including per-cycle detail.
Verbose levels need a debug build

Error and Warn are always compiled in, but Info, Debug, and Trace are stripped from the binary unless LXMASTER was built with LXMASTER_ENABLE_DEBUG. If you set min_level = Trace and see nothing extra, you are almost certainly running a release build — that is expected.

Logging stays off the real-time path

The cyclic RT thread never writes to the log directly; it hands snapshots to a background worker. So enabling logging does not add jitter to the bus — but see the note in the next tutorial about keeping your own loop lean.

Timing and host-level diagnostics

Two kinds of debugging live in their own tutorials because they are deeper topics:

  • Timing quality of your running app — jitter, DC-sync alignment, per-cycle tracing — is measured with the APIs in Real-time behavior and timing.
  • Qualifying the host machine itself — scheduling latency, behavior under load — is done with the CLI: lxmaster diag.

A bring-up failure checklist

When prepare() or start() returns false, work through this:

  1. Read lastError() — it usually names the slave and the reason outright.
  2. Enable cfg.debug at Info (or Debug on a debug build) with the Bringup and State categories to watch the phase walk.
  3. Call reportDeviceStatus() even on a failed start to see how far each device got and its AL status code.
  4. Compare the ENI to the hardware — an identity-mismatch error means the ENI does not match the bus; re-scan and regenerate.

Recap

  • Always check the bool return and print lastError() — it is thread-safe and pinpoints the failure.
  • Call reportDeviceStatus() after stop() to see each device's exit state, AL status, and fault codes.
  • Turn on cfg.debug for a step-by-step log; filter with min_level and category_mask, and send it to a rotating file for deployments.
  • Info/Debug/Trace require a debug build; Error/Warn are always present.